1. Based on Galvatherm 42 in. wide wall panel with 26 ga. exterior and interior steel facers (min. Fy= 37 ksi as per ASTM A653) |
| |
2. Steel facers are prepainted galvanized steel as per ASTM A653 grade 37 (Fy= 37 ksi min). Elasticity Modulus is 29, 000 ksi. |
| |
3. Load Tables were derived from ASTM E72 structural testing. Allowable loads were obtained with 2.5 bending safety factor 3.0 shear safety factor, and deflection limit of L/180. |
| |
4. Thermal load effect due to temperature differential between exterior and interior facers must be considered when applies. |
| |
5. Allowable load is governed by the lowest value of bending strength, shear strength and deflection limit. For allowable load governed by connection, please contact to the technical department. |
| |
6. Foam Insulation factors are based on nominal initial k factor of 0.116 BTU/ft².h.°F tested as per ASTM C518-04 at a mean temperature of 40°F (4°C) |